Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
2500A
Overload release current setting
1000.0 - 2500A
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Rated voltage
690 - 690V
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Degree of protection (IP)
IP30
Motor drive optional
Yes
Motor drive integrated
No
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Back side
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
Complete device with protection unit
Yes
1SDA071707R1 | E2.2S 2500 EKIP G TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
2500A
Overload release current setting
1000.0 .. 2500A
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Rated voltage
690 .. 690V
Integrated earth fault protection
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Degree of protection (IP)
IP30
Motor drive optional
Motor drive integrated
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Back side
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Complete device with protection unit