Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Rated permanent current Iu
2500A
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
Yes
Overload release current setting
1000.0 - 2500A
Rated voltage
690 - 690V
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Type of control element
Push button
With switched-off indicator
Yes
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Motor drive integrated
No
Number of poles
4
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Complete device with protection unit
Yes
Position of connection for main current circuit
Back side
From same serie
1SDA071709R1 | E2.2S 2500 EKIP HI-TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Rated permanent current Iu
2500A
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Overload release current setting
1000.0 .. 2500A
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Type of control element
Push button
With switched-off indicator
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Motor drive integrated
Number of poles
4
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Complete device with protection unit
Position of connection for main current circuit
Back side
From same serie