Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated permanent current Iu
2500A
Rated voltage
690 - 690V
Overload release current setting
1000.0 - 2500A
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Yes
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Number of poles
4
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
No
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally closed contact
0
1SDA071712R1 | E2.2H 2500 EKIP DIP LSI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated permanent current Iu
2500A
Rated voltage
690 .. 690V
Overload release current setting
1000.0 .. 2500A
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Number of poles
4
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
Position of connection for main current circuit
Back side
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally closed contact
0