Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Rated voltage
690 - 690V
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Overload release current setting
1000.0 - 2500A
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Yes
With switched-off indicator
Yes
Number of poles
4
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
No
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Type of control element
Push button
1SDA071717R1 | E2.2H 2500 EKIP G TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Rated voltage
690 .. 690V
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
1000.0 .. 2500A
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
With switched-off indicator
Number of poles
4
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Type of control element
Push button
We use cookies to enhance your experience.