Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
2000A
Adjustment range short-term delayed short-circuit release
1200.0 - 20000A
Device construction
Built-in device fixed built-in technique
Rated voltage
690 - 690V
Integrated earth fault protection
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Type of control element
Push button
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
800.0 - 2000A
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Degree of protection (IP)
IP30
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Complete device with protection unit
Yes
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Yes
From same serie
1SDA071735R1 | E4.2V 2000 EKIP TOUCH LSI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
2000A
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Device construction
Built-in device fixed built-in technique
Rated voltage
690 .. 690V
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Type of control element
Push button
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
800.0 .. 2000A
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Degree of protection (IP)
IP30
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Complete device with protection unit
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Motor drive optional
From same serie