Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Overload release current setting
1000.0 - 2500A
Rated permanent current Iu
2500A
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Bolt connection
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Position of connection for main current circuit
Back side
With switched-off indicator
Yes
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Type of control element
Push button
Number of auxiliary contacts as normally closed contact
0
From same serie
1SDA071759R1 | E4.2V 2500 EKIP HI-TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Overload release current setting
1000.0 .. 2500A
Rated permanent current Iu
2500A
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Position of connection for main current circuit
Back side
With switched-off indicator
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30
Complete device with protection unit
Type of control element
Push button
Number of auxiliary contacts as normally closed contact
0
From same serie