Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
1280.0 - 3200A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Number of auxiliary contacts as change-over contact
4
Rated permanent current Iu
3200A
With switched-off indicator
Yes
Rated voltage
690 - 690V
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
DIN rail (top hat rail) mounting optional
No
Complete device with protection unit
Yes
Device construction
Built-in device fixed built-in technique
Type of control element
Push button
Motor drive optional
Yes
Position of connection for main current circuit
Back side
Motor drive integrated
No
Degree of protection (IP)
IP30
From same serie
1SDA071781R1 | E4.2S 3200 EKIP DIP LI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
1280.0 .. 3200A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Number of auxiliary contacts as change-over contact
4
Rated permanent current Iu
3200A
With switched-off indicator
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
DIN rail (top hat rail) mounting optional
Complete device with protection unit
Device construction
Built-in device fixed built-in technique
Type of control element
Push button
Motor drive optional
Position of connection for main current circuit
Back side
Motor drive integrated
Degree of protection (IP)
IP30