Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Rated permanent current Iu
3200A
Overload release current setting
1280.0 - 3200A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Integrated earth fault protection
No
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
Number of poles
4
Type of control element
Push button
Motor drive optional
Yes
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device fixed built-in technique
1SDA071801R1 | E4.2V 3200 EKIP DIP LI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Rated permanent current Iu
3200A
Overload release current setting
1280.0 .. 3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive integrated
Number of poles
4
Type of control element
Push button
Motor drive optional
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device fixed built-in technique