Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
1600.0 - 4000A
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
No
Complete device with protection unit
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Rated permanent current Iu
4000A
Device construction
Built-in device fixed built-in technique
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
Type of electrical connection of main circuit
Bolt connection
Type of control element
Push button
1SDA071829R1 | E4.2N 4000 EKIP HI-TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
1600.0 .. 4000A
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Complete device with protection unit
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Rated permanent current Iu
4000A
Device construction
Built-in device fixed built-in technique
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
Type of electrical connection of main circuit
Bolt connection
Type of control element
Push button