

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Overload release current setting
1600.0 - 4000A
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Yes
Number of auxiliary contacts as change-over contact
4
Number of poles
4
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Rated permanent current Iu
4000A
Complete device with protection unit
Yes
Position of connection for main current circuit
Back side
Type of control element
Push button
Motor drive integrated
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
From same serie
1SDA071863R1 | E6.2H 4000 EKIP DIP LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Overload release current setting
1600.0 .. 4000A
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
Number of poles
4
DIN rail (top hat rail) mounting optional
With switched-off indicator
Rated permanent current Iu
4000A
Complete device with protection unit
Position of connection for main current circuit
Back side
Type of control element
Push button
Motor drive integrated
Degree of protection (IP)
IP30
Motor drive optional
From same serie
We use cookies to enhance your experience.