Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
1600.0 - 4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Rated permanent current Iu
4000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
6000.0 - 60000A
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
No
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Yes
Number of poles
4
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Yes
Complete device with protection unit
Yes
Type of control element
Push button
Position of connection for main current circuit
Back side
Motor drive integrated
No
From same serie
1SDA071878R1 | E6.2V 4000 EKIP HI-TOUCH LSI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
1600.0 .. 4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Rated permanent current Iu
4000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Number of poles
4
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Complete device with protection unit
Type of control element
Push button
Position of connection for main current circuit
Back side
Motor drive integrated
From same serie