Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Integrated earth fault protection
Yes
Rated permanent current Iu
6300A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Overload release current setting
2520.0 - 6300A
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
4
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 - 690V
Type of control element
Push button
With switched-off indicator
Yes
Adjustment range short-term delayed short-circuit release
3780.0 - 63000A
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
1SDA071929R1 | E6.2H 6300 EKIP HI-TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Integrated earth fault protection
Rated permanent current Iu
6300A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Overload release current setting
2520.0 .. 6300A
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Number of poles
4
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 .. 690V
Type of control element
Push button
With switched-off indicator
Adjustment range short-term delayed short-circuit release
3780.0 .. 63000A
Position of connection for main current circuit
Back side
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive integrated