Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
4000A
Overload release current setting
1600.0 - 4000A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Yes
Position of connection for main current circuit
Back side
DIN rail (top hat rail) mounting optional
No
Number of poles
4
Complete device with protection unit
Yes
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
No
With under voltage release
No
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional
Yes
1SDA071968R1 | E6.2V/F 4000 EKIP HI-TOUCH LSI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
4000A
Overload release current setting
1600.0 .. 4000A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Position of connection for main current circuit
Back side
DIN rail (top hat rail) mounting optional
Number of poles
4
Complete device with protection unit
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
With under voltage release
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional