Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated voltage
690 - 690V
Rated permanent current Iu
5000A
Overload release current setting
2000.0 - 5000A
Adjustment range short-term delayed short-circuit release
3000.0 - 50000A
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Number of poles
4
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
1SDA071990R1 | E6.2H/F 5000 EKIP G HI-TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated voltage
690 .. 690V
Rated permanent current Iu
5000A
Overload release current setting
2000.0 .. 5000A
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Number of poles
4
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
We use cookies to enhance your experience.