Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
3780.0 - 63000A
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Suitable for DIN rail (top hat rail) mounting
No
Rated permanent current Iu
6300A
Overload release current setting
2520.0 - 6300A
Rated voltage
690 - 690V
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Back side
Motor drive integrated
No
Type of control element
Push button
With switched-off indicator
Yes
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Number of poles
4
Complete device with protection unit
Yes
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
4
From same serie
1SDA072017R1 | E6.2H/F 6300 EKIP G TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
3780.0 .. 63000A
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
6300A
Overload release current setting
2520.0 .. 6300A
Rated voltage
690 .. 690V
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Back side
Motor drive integrated
Type of control element
Push button
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Number of poles
4
Complete device with protection unit
Motor drive optional
Number of auxiliary contacts as change-over contact
4
From same serie