Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated permanent current Iu
6300A
Adjustment range short-term delayed short-circuit release
3780.0 - 63000A
Overload release current setting
2520.0 - 6300A
Rated voltage
690 - 690V
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
Yes
With switched-off indicator
Yes
Number of poles
4
Device construction
Built-in device fixed built-in technique
Type of control element
Push button
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Motor drive integrated
No
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Yes
Motor drive optional
Yes
1SDA072020R1 | E6.2H/F 6300 EKIP G HI-TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated permanent current Iu
6300A
Adjustment range short-term delayed short-circuit release
3780.0 .. 63000A
Overload release current setting
2520.0 .. 6300A
Rated voltage
690 .. 690V
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
With switched-off indicator
Number of poles
4
Device construction
Built-in device fixed built-in technique
Type of control element
Push button
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Motor drive optional