

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2520.0 - 6300A
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Rated permanent current Iu
6300A
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 - 690V
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Adjustment range short-term delayed short-circuit release
3780.0 - 63000A
Type of control element
Push button
Number of poles
4
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
With switched-off indicator
Yes
Motor drive optional
Yes
1SDA072022R1 | E6.2V/F 6300 EKIP DIP LSI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2520.0 .. 6300A
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Rated permanent current Iu
6300A
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 .. 690V
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Adjustment range short-term delayed short-circuit release
3780.0 .. 63000A
Type of control element
Push button
Number of poles
4
Position of connection for main current circuit
Back side
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive integrated
With switched-off indicator
Motor drive optional
We use cookies to enhance your experience.