Aleta.hr
Main Product Image

1SDA072025R1 | E6.2V/F 6300 EKIP TOUCH LSI 4P FHR

Code: 1614861

ManufacturerABB
Catalog number1SDA072025R1
Type
EAN code8015644758752

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting2520.0 - 6300A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Adjustment range short-term delayed short-circuit release3780.0 - 63000A
Type of electrical connection of main circuitBolt connection
Motor drive integratedNo
Number of auxiliary contacts as change-over contact4
Adjustment range undelayed short-circuit release9450.0 - 94500A
DIN rail (top hat rail) mounting optionalNo
Rated voltage690 - 690V
Motor drive optionalYes
Degree of protection (IP)IP30
Type of control elementPush button
With switched-off indicatorYes
Device constructionBuilt-in device fixed built-in technique
Position of connection for main current circuitBack side
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
Integrated earth fault protectionNo
Complete device with protection unitYes
Suitable for DIN rail (top hat rail) mountingNo
Number of poles4
Rated permanent current Iu6300A
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072025R1 | E6.2V/F 6300 EKIP TOUCH LSI 4P FHR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting

2520.0 .. 6300A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

With integrated under voltage release

Adjustment range short-term delayed short-circuit release

3780.0 .. 63000A

Type of electrical connection of main circuit

Bolt connection

Motor drive integrated

Number of auxiliary contacts as change-over contact

4

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

DIN rail (top hat rail) mounting optional

Rated voltage

690 .. 690V

Motor drive optional

Degree of protection (IP)

IP30

Type of control element

Push button

With switched-off indicator

Device construction

Built-in device fixed built-in technique

Position of connection for main current circuit

Back side

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Integrated earth fault protection

Complete device with protection unit

Suitable for DIN rail (top hat rail) mounting

Number of poles

4

Rated permanent current Iu

6300A

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.