Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Rated permanent current Iu
6300A
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
3780.0 - 63000A
Overload release current setting
2520.0 - 6300A
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Type of control element
Push button
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
1SDA072029R1 | E6.2V/F 6300 EKIP HI-TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Rated permanent current Iu
6300A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
3780.0 .. 63000A
Overload release current setting
2520.0 .. 6300A
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Back side
Complete device with protection unit
Type of control element
Push button
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
With switched-off indicator