Aleta.hr
Main Product Image

1SDA072030R1 | E6.2V/F 6300 EKIP G HI-TOUCH LSIG 4P FHR

Code: 1614866

ManufacturerRAZNO
Catalog number1SDA072030R1
Type
EAN code8015644758806

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

No

Rated permanent current Iu

6300A

Adjustment range short-term delayed short-circuit release

3780.0 - 63000A

Overload release current setting

2520.0 - 6300A

Suitable for DIN rail (top hat rail) mounting

No

Rated voltage

690 - 690V

Type of electrical connection of main circuit

Bolt connection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Position of connection for main current circuit

Back side

DIN rail (top hat rail) mounting optional

No

Adjustment range undelayed short-circuit release

9450.0 - 94500A

With switched-off indicator

Yes

Type of control element

Push button

Number of auxiliary contacts as normally open contact

0

Motor drive integrated

No

Number of poles

4

Integrated earth fault protection

Yes

Number of auxiliary contacts as change-over contact

4

Motor drive optional

Yes

Complete device with protection unit

Yes

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally closed contact

0

Degree of protection (IP)

IP30


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA072030R1 | E6.2V/F 6300 EKIP G HI-TOUCH LSIG 4P FHR

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

6300A

Adjustment range short-term delayed short-circuit release

3780.0 .. 63000A

Overload release current setting

2520.0 .. 6300A

Suitable for DIN rail (top hat rail) mounting

Rated voltage

690 .. 690V

Type of electrical connection of main circuit

Bolt connection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Position of connection for main current circuit

Back side

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

With switched-off indicator

Type of control element

Push button

Number of auxiliary contacts as normally open contact

0

Motor drive integrated

Number of poles

4

Integrated earth fault protection

Number of auxiliary contacts as change-over contact

4

Motor drive optional

Complete device with protection unit

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally closed contact

0

Degree of protection (IP)

IP30