Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
250A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Adjustment range short-term delayed short-circuit release
150.0 - 2500A
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
375.0 - 3750A
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Number of poles
3
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Overload release current setting
100.0 - 250A
Complete device with protection unit
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
From same serie
1SDA072047R1 | E1.2N 250 EKIP G TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
250A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Adjustment range short-term delayed short-circuit release
150.0 .. 2500A
Integrated earth fault protection
Adjustment range undelayed short-circuit release
375.0 .. 3750A
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Number of poles
3
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Overload release current setting
100.0 .. 250A
Complete device with protection unit
Motor drive integrated
Degree of protection (IP)
IP30
Motor drive optional