Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu630A
Overload release current setting252.0 - 630A
Number of poles3
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Adjustment range short-term delayed short-circuit release378.0 - 6300A
With switched-off indicatorYes
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Motor drive integratedNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
Type of control elementPush button
Type of electrical connection of main circuitConnection at separate chassis part
Suitable for DIN rail (top hat rail) mountingNo
Rated voltage690 - 690V
Number of auxiliary contacts as change-over contact4
Motor drive optionalYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Complete device with protection unitYes
Adjustment range undelayed short-circuit release945.0 - 9450A
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072053R1 | E1.2B 630 EKIP DIP LSIG 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

630A

Overload release current setting

252.0 .. 630A

Number of poles

3

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

With integrated under voltage release

Adjustment range short-term delayed short-circuit release

378.0 .. 6300A

With switched-off indicator

Position of connection for main current circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Motor drive integrated

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

Type of control element

Push button

Type of electrical connection of main circuit

Connection at separate chassis part

Suitable for DIN rail (top hat rail) mounting

Rated voltage

690 .. 690V

Number of auxiliary contacts as change-over contact

4

Motor drive optional

Device construction

Built-in device slide-in technique (withdrawable)

Complete device with protection unit

Adjustment range undelayed short-circuit release

945.0 .. 9450A

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.