Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Overload release current setting500.0 - 1250A
Number of poles3
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
Rated permanent current Iu1250A
Rated voltage690 - 690V
With switched-off indicatorYes
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Adjustment range short-term delayed short-circuit release750.0 - 12500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Complete device with protection unitYes
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release1875.0 - 18750A
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Type of control elementPush button
Suitable for DIN rail (top hat rail) mountingNo
With under voltage releaseNo
Integrated earth fault protectionNo
Motor drive optionalYes
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072188R1 | E1.2C 1250 EKIP HI-TOUCH LSI 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Overload release current setting

500.0 .. 1250A

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

1250A

Rated voltage

690 .. 690V

With switched-off indicator

Position of connection for main current circuit

Connection at separate chassis part

Motor drive integrated

Adjustment range short-term delayed short-circuit release

750.0 .. 12500A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Complete device with protection unit

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

Type of control element

Push button

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Integrated earth fault protection

Motor drive optional

Degree of protection (IP)

IP30