Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Overload release current setting
500.0 - 1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated permanent current Iu
1250A
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional
Yes
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
With switched-off indicator
Yes
Complete device with protection unit
Yes
Motor drive integrated
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
1SDA072190R1 | E1.2C 1250 EKIP G HI-TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Overload release current setting
500.0 .. 1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated permanent current Iu
1250A
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
With switched-off indicator
Complete device with protection unit
Motor drive integrated
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0