Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage releaseNo
Rated permanent current Iu1250A
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range short-term delayed short-circuit release750.0 - 12500A
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Number of poles3
With switched-off indicatorYes
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Device constructionBuilt-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release1875.0 - 18750A
Type of control elementPush button
Position of connection for main current circuitConnection at separate chassis part
Complete device with protection unitYes
Number of auxiliary contacts as normally open contact0
Motor drive optionalYes
Motor drive integratedNo
Overload release current setting500.0 - 1250A
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072198R1 | E1.2N 1250 EKIP HI-TOUCH LSI 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

1250A

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

66kA

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range short-term delayed short-circuit release

750.0 .. 12500A

Integrated earth fault protection

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Number of poles

3

With switched-off indicator

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Device construction

Built-in device slide-in technique (withdrawable)

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Type of control element

Push button

Position of connection for main current circuit

Connection at separate chassis part

Complete device with protection unit

Number of auxiliary contacts as normally open contact

0

Motor drive optional

Motor drive integrated

Overload release current setting

500.0 .. 1250A

Degree of protection (IP)

IP30

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.