Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1600A
Overload release current setting
640.0 - 1600A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
With switched-off indicator
Yes
Number of poles
3
Motor drive optional
Yes
Type of control element
Push button
Motor drive integrated
No
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
From same serie
1SDA072218R1 | E1.2B 1600 EKIP HI-TOUCH LSI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1600A
Overload release current setting
640.0 .. 1600A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
With switched-off indicator
Number of poles
3
Motor drive optional
Type of control element
Push button
Motor drive integrated
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30