Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Rated permanent current Iu
1600A
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Overload release current setting
640.0 - 1600A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Type of control element
Push button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Integrated earth fault protection
No
Motor drive optional
Yes
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
With switched-off indicator
Yes
Complete device with protection unit
Yes
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive integrated
No
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
2400.0 - 24000A
1SDA072225R1 | E1.2C 1600 EKIP TOUCH LSI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
1600A
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Overload release current setting
640.0 .. 1600A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Type of control element
Push button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Integrated earth fault protection
Motor drive optional
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
With switched-off indicator
Complete device with protection unit
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive integrated
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
We use cookies to enhance your experience.