Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Rated permanent current Iu
800A
Overload release current setting
320.0 - 800A
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
1200.0 - 12000A
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
Complete device with protection unit
Yes
With under voltage release
No
Integrated earth fault protection
No
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Motor drive optional
Yes
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Number of poles
3
From same serie
1SDA072248R1 | E2.2N 800 EKIP HI-TOUCH LSI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Rated permanent current Iu
800A
Overload release current setting
320.0 .. 800A
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Complete device with protection unit
With under voltage release
Integrated earth fault protection
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Motor drive optional
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Number of poles
3
From same serie