Aleta.hr
Main Product Image

1SDA072258R1 | E2.2S 800 EKIP HI-TOUCH LSI 3P WMP

Code: 1615044

ManufacturerRAZNO
Catalog number1SDA072258R1
Type
EAN code8015644761080

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

No

Rated voltage

690 - 690V

Overload release current setting

320.0 - 800A

Adjustment range short-term delayed short-circuit release

480.0 - 8000A

Integrated earth fault protection

No

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Device construction

Built-in device slide-in technique (withdrawable)

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range undelayed short-circuit release

1200.0 - 12000A

Rated permanent current Iu

800A

Suitable for DIN rail (top hat rail) mounting

No

DIN rail (top hat rail) mounting optional

No

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Number of auxiliary contacts as normally closed contact

0

Complete device with protection unit

Yes

Motor drive optional

Yes

Motor drive integrated

No

With switched-off indicator

Yes

Degree of protection (IP)

IP30

Number of poles

3


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA072258R1 | E2.2S 800 EKIP HI-TOUCH LSI 3P WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated voltage

690 .. 690V

Overload release current setting

320.0 .. 800A

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Integrated earth fault protection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Device construction

Built-in device slide-in technique (withdrawable)

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Rated permanent current Iu

800A

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Number of auxiliary contacts as normally closed contact

0

Complete device with protection unit

Motor drive optional

Motor drive integrated

With switched-off indicator

Degree of protection (IP)

IP30

Number of poles

3

From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

We use cookies to enhance your experience.