Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
800A
Integrated earth fault protection
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Overload release current setting
320.0 - 800A
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
With switched-off indicator
Yes
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional
Yes
Motor drive integrated
No
From same serie
1SDA072263R1 | E2.2H 800 EKIP DIP LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
800A
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Overload release current setting
320.0 .. 800A
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
With switched-off indicator
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional
Motor drive integrated
From same serie