Technical specifications

Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
Degree of protection (IP)IP30
Motor drive integratedNo
Position of connection for main current circuitConnection at separate chassis part
Overload release current setting320.0 - 800A
Type of control elementPush button
Number of poles3
Number of auxiliary contacts as normally closed contact0
Rated voltage690 - 690V
Type of electrical connection of main circuitConnection at separate chassis part
With integrated under voltage releaseNo
Suitable for DIN rail (top hat rail) mountingNo
Rated permanent current Iu800A
Integrated earth fault protectionYes
Motor drive optionalYes
Adjustment range undelayed short-circuit release1200.0 - 12000A
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Device constructionBuilt-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact0
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072263R1 | E2.2H 800 EKIP DIP LSIG 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Degree of protection (IP)

IP30

Motor drive integrated

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

320.0 .. 800A

Type of control element

Push button

Number of poles

3

Number of auxiliary contacts as normally closed contact

0

Rated voltage

690 .. 690V

Type of electrical connection of main circuit

Connection at separate chassis part

With integrated under voltage release

Suitable for DIN rail (top hat rail) mounting

Rated permanent current Iu

800A

Integrated earth fault protection

Motor drive optional

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Device construction

Built-in device slide-in technique (withdrawable)

Number of auxiliary contacts as normally open contact

0

Complete device with protection unit

DIN rail (top hat rail) mounting optional