Aleta.hr
Main Product Image

1SDA072263R1 | E2.2H 800 EKIP DIP LSIG 3P WMP

Code: 1615049

ManufacturerABB
Catalog number1SDA072263R1
EAN code8015644761134

















Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage releaseNo
Rated permanent current Iu800A
Integrated earth fault protectionYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as change-over contact4
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release1200.0 - 12000A
Device constructionBuilt-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Overload release current setting320.0 - 800A
Number of auxiliary contacts as normally closed contact0
Suitable for DIN rail (top hat rail) mountingNo
Rated voltage690 - 690V
With switched-off indicatorYes
Number of poles3
Position of connection for main current circuitConnection at separate chassis part
Complete device with protection unitYes
Degree of protection (IP)IP30
Type of control elementPush button
Motor drive optionalYes
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072263R1 | E2.2H 800 EKIP DIP LSIG 3P WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

800A

Integrated earth fault protection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Number of auxiliary contacts as normally open contact

0

Type of electrical connection of main circuit

Connection at separate chassis part

Number of auxiliary contacts as change-over contact

4

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Device construction

Built-in device slide-in technique (withdrawable)

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Overload release current setting

320.0 .. 800A

Number of auxiliary contacts as normally closed contact

0

Suitable for DIN rail (top hat rail) mounting

Rated voltage

690 .. 690V

With switched-off indicator

Number of poles

3

Position of connection for main current circuit

Connection at separate chassis part

Complete device with protection unit

Degree of protection (IP)

IP30

Type of control element

Push button

Motor drive optional

Motor drive integrated

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.