Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1000A
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
With under voltage release
No
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Rated voltage
690 - 690V
Degree of protection (IP)
IP30
Integrated earth fault protection
No
Number of poles
3
Overload release current setting
400.0 - 1000A
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive optional
Yes
Type of control element
Push button
Motor drive integrated
No
Complete device with protection unit
Yes
1SDA072274R1 | E2.2N 1000 EKIP TOUCH LI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1000A
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With under voltage release
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Rated voltage
690 .. 690V
Degree of protection (IP)
IP30
Integrated earth fault protection
Number of poles
3
Overload release current setting
400.0 .. 1000A
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive optional
Type of control element
Push button
Motor drive integrated
Complete device with protection unit