Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1000A
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
400.0 - 1000A
Rated voltage
690 - 690V
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
Yes
Number of poles
3
With switched-off indicator
Yes
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
1SDA072299R1 | E2.2H 1000 EKIP HI-TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1000A
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
400.0 .. 1000A
Rated voltage
690 .. 690V
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
Number of poles
3
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Degree of protection (IP)
IP30
Motor drive integrated
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
We use cookies to enhance your experience.