Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
500.0 - 1250A
Integrated earth fault protection
No
Motor drive integrated
No
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
DIN rail (top hat rail) mounting optional
No
Rated permanent current Iu
1250A
Degree of protection (IP)
IP30
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Position of connection for main current circuit
Connection at separate chassis part
Rated voltage
690 - 690V
With under voltage release
No
Type of control element
Push button
With switched-off indicator
Yes
Number of poles
3
From same serie
1SDA072312R1 | E2.2S 1250 EKIP DIP LSI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
500.0 .. 1250A
Integrated earth fault protection
Motor drive integrated
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
1250A
Degree of protection (IP)
IP30
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Position of connection for main current circuit
Connection at separate chassis part
Rated voltage
690 .. 690V
With under voltage release
Type of control element
Push button
With switched-off indicator
Number of poles
3
From same serie