Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA072317R1 | E2.2S 1250 EKIP G TOUCH LSIG 3P WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
With integrated under voltage release
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Number of poles
3
Integrated earth fault protection
Position of connection for main current circuit
Connection at separate chassis part
Rated permanent current Iu
1250A
Type of control element
Push button
Motor drive integrated
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
500.0 .. 1250A
Motor drive optional
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
DIN rail (top hat rail) mounting optional