Aleta.hr
Main Product Image

1SDA072321R1 | E2.2H 1250 EKIP DIP LI 3P WMP

Code: 1615107

ManufacturerABB
Catalog number1SDA072321R1
EAN code8015644761714

















Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release- - -A
With integrated under voltage releaseNo
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release1875.0 - 18750A
Integrated earth fault protectionNo
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Overload release current setting500.0 - 1250A
With switched-off indicatorYes
Number of auxiliary contacts as normally closed contact0
Rated voltage690 - 690V
Degree of protection (IP)IP30
Complete device with protection unitYes
Suitable for DIN rail (top hat rail) mountingNo
Number of poles3
Rated permanent current Iu1250A
Number of auxiliary contacts as change-over contact4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Motor drive integratedNo
Type of control elementPush button
Number of auxiliary contacts as normally open contact0
Motor drive optionalYes
Position of connection for main current circuitConnection at separate chassis part
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072321R1 | E2.2H 1250 EKIP DIP LI 3P WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release

- .. -A

With integrated under voltage release

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Integrated earth fault protection

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

Overload release current setting

500.0 .. 1250A

With switched-off indicator

Number of auxiliary contacts as normally closed contact

0

Rated voltage

690 .. 690V

Degree of protection (IP)

IP30

Complete device with protection unit

Suitable for DIN rail (top hat rail) mounting

Number of poles

3

Rated permanent current Iu

1250A

Number of auxiliary contacts as change-over contact

4

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Motor drive integrated

Type of control element

Push button

Number of auxiliary contacts as normally open contact

0

Motor drive optional

Position of connection for main current circuit

Connection at separate chassis part

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.