Aleta.hr
Main Product Image

1SDA072323R1 | E2.2H 1250 EKIP DIP LSIG 3P WMP

Code: 1615109

ManufacturerABB
Catalog number1SDA072323R1
EAN code8015644761738

















Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage releaseNo
Rated permanent current Iu1250A
Overload release current setting500.0 - 1250A
Rated voltage690 - 690V
Adjustment range short-term delayed short-circuit release750.0 - 12500A
Integrated earth fault protectionYes
Type of electrical connection of main circuitConnection at separate chassis part
Device constructionBuilt-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release1875.0 - 18750A
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
Position of connection for main current circuitConnection at separate chassis part
Motor drive optionalYes
Motor drive integratedNo
Number of poles3
Type of control elementPush button
Complete device with protection unitYes
Degree of protection (IP)IP30
Number of auxiliary contacts as normally open contact0
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072323R1 | E2.2H 1250 EKIP DIP LSIG 3P WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

1250A

Overload release current setting

500.0 .. 1250A

Rated voltage

690 .. 690V

Adjustment range short-term delayed short-circuit release

750.0 .. 12500A

Integrated earth fault protection

Type of electrical connection of main circuit

Connection at separate chassis part

Device construction

Built-in device slide-in technique (withdrawable)

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Suitable for DIN rail (top hat rail) mounting

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Position of connection for main current circuit

Connection at separate chassis part

Motor drive optional

Motor drive integrated

Number of poles

3

Type of control element

Push button

Complete device with protection unit

Degree of protection (IP)

IP30

Number of auxiliary contacts as normally open contact

0

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.