

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Integrated earth fault protection
Yes
Rated voltage
690 - 690V
Overload release current setting
640.0 - 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Rated permanent current Iu
1600A
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
2400.0 - 24000A
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Motor drive optional
Yes
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Type of control element
Push button
Degree of protection (IP)
IP30
Number of poles
3
Motor drive integrated
No
From same serie
1SDA072339R1 | E2.2B 1600 EKIP HI-TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Integrated earth fault protection
Rated voltage
690 .. 690V
Overload release current setting
640.0 .. 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Rated permanent current Iu
1600A
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Motor drive optional
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Type of control element
Push button
Degree of protection (IP)
IP30
Number of poles
3
Motor drive integrated
From same serie
We use cookies to enhance your experience.