Technical specifications

Type of control elementPush button
Number of auxiliary contacts as normally closed contact0
Rated voltage690 - 690V
Degree of protection (IP)IP30
Number of auxiliary contacts as normally open contact0
Motor drive integratedNo
Rated permanent current Iu1600A
Overload release current setting640.0 - 1600A
Position of connection for main current circuitConnection at separate chassis part
Number of auxiliary contacts as change-over contact4
Number of poles3
Type of electrical connection of main circuitConnection at separate chassis part
With switched-off indicatorYes
Complete device with protection unitYes
With under voltage releaseNo
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release2400.0 - 24000A
Adjustment range short-term delayed short-circuit release960.0 - 16000A
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072348R1 | E2.2N 1600 EKIP HI-TOUCH LSI 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Type of control element

Push button

Number of auxiliary contacts as normally closed contact

0

Rated voltage

690 .. 690V

Degree of protection (IP)

IP30

Number of auxiliary contacts as normally open contact

0

Motor drive integrated

Rated permanent current Iu

1600A

Overload release current setting

640.0 .. 1600A

Position of connection for main current circuit

Connection at separate chassis part

Number of auxiliary contacts as change-over contact

4

Number of poles

3

Type of electrical connection of main circuit

Connection at separate chassis part

With switched-off indicator

Complete device with protection unit

With under voltage release

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

66kA

DIN rail (top hat rail) mounting optional

Device construction

Built-in device slide-in technique (withdrawable)

Integrated earth fault protection

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A