Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
640.0 - 1600A
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Rated permanent current Iu
1600A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Complete device with protection unit
Yes
With switched-off indicator
Yes
Type of control element
Push button
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Motor drive integrated
No
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
From same serie
1SDA072360R1 | E2.2S 1600 EKIP G HI-TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
640.0 .. 1600A
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Rated permanent current Iu
1600A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Complete device with protection unit
With switched-off indicator
Type of control element
Push button
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
From same serie