Technical specifications

Rated permanent current Iu1600A
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
Overload release current setting640.0 - 1600A
Type of electrical connection of main circuitConnection at separate chassis part
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Number of auxiliary contacts as normally open contact0
Rated voltage690 - 690V
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Number of poles3
With integrated under voltage releaseNo
Type of control elementPush button
Motor drive integratedNo
Adjustment range short-term delayed short-circuit release960.0 - 16000A
Motor drive optionalYes
Adjustment range undelayed short-circuit release2400.0 - 24000A
Complete device with protection unitYes
Integrated earth fault protectionYes
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072363R1 | E2.2H 1600 EKIP DIP LSIG 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

1600A

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

640.0 .. 1600A

Type of electrical connection of main circuit

Connection at separate chassis part

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Number of auxiliary contacts as normally open contact

0

Rated voltage

690 .. 690V

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Number of poles

3

With integrated under voltage release

Type of control element

Push button

Motor drive integrated

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

Motor drive optional

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Complete device with protection unit

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Device construction

Built-in device slide-in technique (withdrawable)