Aleta.hr
Main Product Image

1SDA072363R1 | E2.2H 1600 EKIP DIP LSIG 3P WMP

Code: 1615149

ManufacturerRAZNO
Catalog number1SDA072363R1
Type
EAN code8015644762131

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

No

Rated permanent current Iu

1600A

Device construction

Built-in device slide-in technique (withdrawable)

Integrated earth fault protection

Yes

Rated voltage

690 - 690V

Type of control element

Push button

Number of auxiliary contacts as change-over contact

4

Motor drive optional

Yes

Suitable for DIN rail (top hat rail) mounting

No

Motor drive integrated

No

Degree of protection (IP)

IP30

Adjustment range undelayed short-circuit release

2400.0 - 24000A

Number of poles

3

Number of auxiliary contacts as normally closed contact

0

Complete device with protection unit

Yes

DIN rail (top hat rail) mounting optional

No

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

640.0 - 1600A

Type of electrical connection of main circuit

Connection at separate chassis part

Number of auxiliary contacts as normally open contact

0

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

With switched-off indicator

Yes

Adjustment range short-term delayed short-circuit release

960.0 - 16000A

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA072363R1 | E2.2H 1600 EKIP DIP LSIG 3P WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

1600A

Device construction

Built-in device slide-in technique (withdrawable)

Integrated earth fault protection

Rated voltage

690 .. 690V

Type of control element

Push button

Number of auxiliary contacts as change-over contact

4

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

Motor drive integrated

Degree of protection (IP)

IP30

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Number of poles

3

Number of auxiliary contacts as normally closed contact

0

Complete device with protection unit

DIN rail (top hat rail) mounting optional

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

640.0 .. 1600A

Type of electrical connection of main circuit

Connection at separate chassis part

Number of auxiliary contacts as normally open contact

0

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

With switched-off indicator

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.