Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage releaseNo
Rated permanent current Iu1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Adjustment range undelayed short-circuit release2400.0 - 24000A
Adjustment range short-term delayed short-circuit release960.0 - 16000A
Integrated earth fault protectionYes
Number of auxiliary contacts as normally open contact0
Rated voltage690 - 690V
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitConnection at separate chassis part
Position of connection for main current circuitConnection at separate chassis part
Suitable for DIN rail (top hat rail) mountingNo
Number of poles3
With switched-off indicatorYes
Complete device with protection unitYes
Number of auxiliary contacts as change-over contact4
Type of control elementPush button
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Motor drive integratedNo
Degree of protection (IP)IP30
Motor drive optionalYes
Overload release current setting640.0 - 1600A
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072367R1 | E2.2H 1600 EKIP G TOUCH LSIG 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

1600A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

Integrated earth fault protection

Number of auxiliary contacts as normally open contact

0

Rated voltage

690 .. 690V

Number of auxiliary contacts as normally closed contact

0

Type of electrical connection of main circuit

Connection at separate chassis part

Position of connection for main current circuit

Connection at separate chassis part

Suitable for DIN rail (top hat rail) mounting

Number of poles

3

With switched-off indicator

Complete device with protection unit

Number of auxiliary contacts as change-over contact

4

Type of control element

Push button

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

Motor drive integrated

Degree of protection (IP)

IP30

Motor drive optional

Overload release current setting

640.0 .. 1600A

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.