Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Integrated earth fault protection
Yes
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 - 690V
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
3
With switched-off indicator
Yes
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
Overload release current setting
640.0 - 1600A
From same serie
1SDA072367R1 | E2.2H 1600 EKIP G TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Number of poles
3
With switched-off indicator
Complete device with protection unit
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Motor drive integrated
Degree of protection (IP)
IP30
Motor drive optional
Overload release current setting
640.0 .. 1600A