Technical specifications
With integrated under voltage release
No
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated permanent current Iu
2000A
Integrated earth fault protection
Yes
Overload release current setting
800.0 - 2000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
1200.0 - 20000A
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
No
From same serie
1SDA072377R1 | E2.2B 2000 EKIP G TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated permanent current Iu
2000A
Integrated earth fault protection
Overload release current setting
800.0 .. 2000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
DIN rail (top hat rail) mounting optional
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Complete device with protection unit
Motor drive optional
Number of auxiliary contacts as change-over contact
4