Aleta.hr
Main Product Image

1SDA072379R1 | E2.2B 2000 EKIP HI-TOUCH LSIG 3P WMP

Code: 1615165

ManufacturerRAZNO
Catalog number1SDA072379R1
Type
EAN code8015644762292

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

No

Rated permanent current Iu

2000A

Suitable for DIN rail (top hat rail) mounting

No

Type of electrical connection of main circuit

Connection at separate chassis part

Device construction

Built-in device slide-in technique (withdrawable)

Overload release current setting

800.0 - 2000A

Integrated earth fault protection

Yes

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

Adjustment range undelayed short-circuit release

3000.0 - 30000A

DIN rail (top hat rail) mounting optional

No

Rated voltage

690 - 690V

Adjustment range short-term delayed short-circuit release

1200.0 - 20000A

Motor drive integrated

No

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Connection at separate chassis part

Number of poles

3

Type of control element

Push button

With switched-off indicator

Yes

Number of auxiliary contacts as normally open contact

0

Complete device with protection unit

Yes

Number of auxiliary contacts as normally closed contact

0

Motor drive optional

Yes

Degree of protection (IP)

IP30


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA072379R1 | E2.2B 2000 EKIP HI-TOUCH LSIG 3P WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

2000A

Suitable for DIN rail (top hat rail) mounting

Type of electrical connection of main circuit

Connection at separate chassis part

Device construction

Built-in device slide-in technique (withdrawable)

Overload release current setting

800.0 .. 2000A

Integrated earth fault protection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

DIN rail (top hat rail) mounting optional

Rated voltage

690 .. 690V

Adjustment range short-term delayed short-circuit release

1200.0 .. 20000A

Motor drive integrated

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Connection at separate chassis part

Number of poles

3

Type of control element

Push button

With switched-off indicator

Number of auxiliary contacts as normally open contact

0

Complete device with protection unit

Number of auxiliary contacts as normally closed contact

0

Motor drive optional

Degree of protection (IP)

IP30