Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitConnection at separate chassis part
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release3000 - 30000A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Type of control elementPush button
With integrated under voltage releaseNo
Overload release current setting800 - 2000A
Degree of protection (IP)IP30
Adjustment range short-term delayed short-circuit release- - -A
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Complete device with protection unitYes
Rated permanent current Iu2000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA