Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Rated voltage
690 - 690V
Overload release current setting
800.0 - 2000A
Rated permanent current Iu
2000A
Adjustment range short-term delayed short-circuit release
1200.0 - 20000A
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Yes
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
3
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Type of control element
Push button
Motor drive optional
Yes
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
1SDA072389R1 | E2.2N 2000 EKIP HI-TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Rated voltage
690 .. 690V
Overload release current setting
800.0 .. 2000A
Rated permanent current Iu
2000A
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
3
DIN rail (top hat rail) mounting optional
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Complete device with protection unit
Type of control element
Push button
Motor drive optional
Motor drive integrated
Number of auxiliary contacts as change-over contact
4