Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA072392R1 | E2.2S 2000 EKIP DIP LSI 3P WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
2000A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Rated voltage
690 .. 690V
Motor drive integrated
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Type of control element
Push button
Overload release current setting
800.0 .. 2000A
Integrated earth fault protection
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
With integrated under voltage release
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Motor drive optional
Number of poles
3
DIN rail (top hat rail) mounting optional
With switched-off indicator
Complete device with protection unit