Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu2500A
Overload release current setting1000.0 - 2500A
Motor drive integratedNo
Position of connection for main current circuitConnection at separate chassis part
Number of auxiliary contacts as change-over contact4
Type of electrical connection of main circuitConnection at separate chassis part
Degree of protection (IP)IP30
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Number of auxiliary contacts as normally open contact0
Adjustment range undelayed short-circuit release3750.0 - 37500A
Type of control elementPush button
Adjustment range short-term delayed short-circuit release1500.0 - 25000A
Number of poles3
With integrated under voltage releaseNo
With switched-off indicatorYes
Rated voltage690 - 690V
Motor drive optionalYes
Complete device with protection unitYes
Integrated earth fault protectionYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072427R1 | E2.2S 2500 EKIP G TOUCH LSIG 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

2500A

Overload release current setting

1000.0 .. 2500A

Motor drive integrated

Position of connection for main current circuit

Connection at separate chassis part

Number of auxiliary contacts as change-over contact

4

Type of electrical connection of main circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Number of auxiliary contacts as normally open contact

0

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

Type of control element

Push button

Adjustment range short-term delayed short-circuit release

1500.0 .. 25000A

Number of poles

3

With integrated under voltage release

With switched-off indicator

Rated voltage

690 .. 690V

Motor drive optional

Complete device with protection unit

Integrated earth fault protection

Device construction

Built-in device slide-in technique (withdrawable)

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.