Aleta.hr
Main Product Image

1SDA072434R1 | E2.2H 2500 EKIP TOUCH LI 3P WMP

Code: 1615220

ManufacturerRAZNO
Catalog number1SDA072434R1
Type
EAN code8015644762841

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release

- - -A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated voltage

690 - 690V

Adjustment range undelayed short-circuit release

3750.0 - 37500A

Overload release current setting

1000.0 - 2500A

Rated permanent current Iu

2500A

Suitable for DIN rail (top hat rail) mounting

No

Type of electrical connection of main circuit

Connection at separate chassis part

Number of poles

3

Motor drive optional

Yes

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Integrated earth fault protection

No

Number of auxiliary contacts as change-over contact

4

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

No

Type of control element

Push button

Complete device with protection unit

Yes

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Motor drive integrated

No

With under voltage release

No

With switched-off indicator

Yes

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA072434R1 | E2.2H 2500 EKIP TOUCH LI 3P WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release

- .. -A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated voltage

690 .. 690V

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

Overload release current setting

1000.0 .. 2500A

Rated permanent current Iu

2500A

Suitable for DIN rail (top hat rail) mounting

Type of electrical connection of main circuit

Connection at separate chassis part

Number of poles

3

Motor drive optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Integrated earth fault protection

Number of auxiliary contacts as change-over contact

4

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

Type of control element

Push button

Complete device with protection unit

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Motor drive integrated

With under voltage release

With switched-off indicator

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.