Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu2500A
Overload release current setting1000.0 - 2500A
Rated voltage690 - 690V
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Number of poles3
Position of connection for main current circuitConnection at separate chassis part
Type of electrical connection of main circuitConnection at separate chassis part
With switched-off indicatorYes
Degree of protection (IP)IP30
Suitable for DIN rail (top hat rail) mountingNo
Type of control elementPush button
Adjustment range undelayed short-circuit release3750.0 - 37500A
Motor drive integratedNo
Motor drive optionalYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Adjustment range short-term delayed short-circuit release- - -A
Integrated earth fault protectionNo
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072434R1 | E2.2H 2500 EKIP TOUCH LI 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

2500A

Overload release current setting

1000.0 .. 2500A

Rated voltage

690 .. 690V

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Number of poles

3

Position of connection for main current circuit

Connection at separate chassis part

Type of electrical connection of main circuit

Connection at separate chassis part

With switched-off indicator

Degree of protection (IP)

IP30

Suitable for DIN rail (top hat rail) mounting

Type of control element

Push button

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

Motor drive integrated

Motor drive optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Adjustment range short-term delayed short-circuit release

- .. -A

Integrated earth fault protection

With under voltage release

DIN rail (top hat rail) mounting optional

Device construction

Built-in device slide-in technique (withdrawable)

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.