Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated voltage
690 - 690V
Overload release current setting
1280.0 - 3200A
Integrated earth fault protection
No
Rated permanent current Iu
3200A
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
From same serie
1SDA072501R1 | E4.2S 3200 EKIP DIP LI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated voltage
690 .. 690V
Overload release current setting
1280.0 .. 3200A
Integrated earth fault protection
Rated permanent current Iu
3200A
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Type of control element
Push button
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP30
Motor drive integrated
From same serie
We use cookies to enhance your experience.