Aleta.hr
Main Product Image

1SDA072504R1 | E4.2S 3200 EKIP TOUCH LI 3P WMP

Code: 1615260

ManufacturerABB
Catalog number1SDA072504R1
TypeE4.2S 3200 Ekip Touch LI 3p WMP
Category-
EAN code8015644763541

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Overload release current setting1280.0 - 3200A
With switched-off indicatorYes
Motor drive integratedNo
With under voltage releaseNo
Adjustment range undelayed short-circuit release4800.0 - 48000A
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Adjustment range short-term delayed short-circuit release- - -A
Integrated earth fault protectionNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitConnection at separate chassis part
Position of connection for main current circuitConnection at separate chassis part
Complete device with protection unitYes
Type of control elementPush button
Rated permanent current Iu3200A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072504R1 | E4.2S 3200 EKIP TOUCH LI 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP30

Number of auxiliary contacts as change-over contact

4

Overload release current setting

1280.0 .. 3200A

With switched-off indicator

Motor drive integrated

With under voltage release

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

DIN rail (top hat rail) mounting optional

Motor drive optional

Adjustment range short-term delayed short-circuit release

- .. -A

Integrated earth fault protection

Device construction

Built-in device slide-in technique (withdrawable)

Suitable for DIN rail (top hat rail) mounting

Type of electrical connection of main circuit

Connection at separate chassis part

Position of connection for main current circuit

Connection at separate chassis part

Complete device with protection unit

Type of control element

Push button

Rated permanent current Iu

3200A

Number of poles

3

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.